Conduit shall be Anaconda SEALTITE® Type ZHUA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant, flame retardant, LOW SMOKE AND ZERO HALOGEN TPU jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, and IP 67 rated when installed with approved end connectors.
Unit of Measure

Specifications

Type

ZHUA

Electrical Trade Size

4 in103 mm

Length

25 ft7.62 m

Packaging

Standard Carton

Inside Diameter

4.000 to 4.040 in101.600 to 102.616 mm

Outside Diameter

4.460 to 4.500 in113.284 to 114.300 mm

Inside Bend Radius

17 in431.8 mm

Approx. Weight per 100 ft

362 lbs164.2 kg

Color

BLACK

Note

Colors are available upon request.
Test data results obtained from an independent test laboratory. Consult factory for additional details.

Industry Certifications


UL Listed & CSA Certified

Cross-Reference #

6711-22-00 88192 LSZH ZHLA-19

Core Material

Galvanized Steel

Ingress Protection (IP) Rating

Ingress Protection (IP) 66/67

Jacket Material

Thermoplastic Polyurethane (TPU)

Jacket Benefits

Liquid Tight Oil Resistant Zero Halogen

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Article 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; and NEC Article 350.

NEC Articles

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A For Restricted or Self-Contained Ventilation Areas
Temperature ranges -40°F to + 176°F (-40°C to +80°C)

MEETS or EXCEEDS the following Standards

N/A

  • Flame Spread Index ASTM E162
  • Smoke Density (Generation) ASTM E662
  • Toxic Gas Generation Bombardier SMP-800C
  • Jacket Material is U.L. 94 Certified
  • Conduit is U.L. 360 Listed