Thermoplastic PVC jacket with integral bonding wire 3/8" through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type HTUA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, CSA certified and IP 67 rated
more
Unit of Measure

Specifications

Type

HTUA

Electrical Trade Size

1 in27 mm

Length

100 ft30.48 m

Packaging

Small Cartons

Inside Diameter

1.041 to 1.066 in26.441 to 27.076 mm

Outside Diameter

1.290 to 1.315 in32.766 to 33.401 mm

Approx. Inside Bend Radius

6.0 in152.4 mm

Approx. Weight per 100 ft

73 lbs33.11 kg

Color

GRAY

Optional Colors

Black

Industry Certifications


UL Listed & CSA Certified



Cross-Reference #

55-28-84-01 6904-30-00 80232 ATLA-13

Core Material

Galvanized Steel

Ingress Protection (IP) Rating

Ingress Protection (IP) 66/67

Jacket Material

Polyvinyl Chloride (PVC)

Jacket Benefits

Extreme Cold High Heat Liquid Tight Oil Resistant

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations Rated for temperature ranges UL temps -51ºF to + 221ºF (-46ºC to +105ºC), CSA -51ºF to 167ºF (-46ºC to +75ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

NEC Articles

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A Ideal for Use in Environments with Extreme Temperatures and UL Listing is Required
Temperature Range: -51ºF to +221ºF (-46ºC to +105ºC)