Thermoplastic PVC jacket no bonding wire
Conduit shall be Anaconda SEALTITE® Type EF. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with sunlight resistant PVC outer jacket. Type EF conduit shall be used for applications where agency approvals are not required. Conduit IP 67 rated when installed with approved end connectors.
Conduit shall be Anaconda SEALTITE® Type EF. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with sunlight resistant PVC outer jacket. Type EF conduit shall be used for applications where agency approvals are not required. Conduit IP 67 rated when installed with approved end connectors.
Unit of Measure
Specifications
Type |
N/A EF |
Electrical Trade Size |
N/A 3/8 in12 mm |
Length |
N/A 800 ft243.84 m |
Packaging |
N/A Small Reels |
Inside Diameter |
N/A 0.485 to 0.505 in12.319 to 12.827 mm |
Outside Diameter |
N/A 0.690 to 0.710 in17.526 to 18.034 mm |
Approx. Inside Bend Radius |
N/A 2.0 in50.8 mm |
Approx. Weight per 100 ft |
N/A 17 lbs7.71 kg |
Color |
N/A GRAY |
Note |
N/A Standard SEALTITE® Type EFST is recommended in sizes above 2" |
Industry Certifications |
N/A
RoHS WEEE |
Cross-Reference # |
N/A 80103 80104 EF-10 EFLT EFLT-3/8 EXLT EXLT-3/8 |
Core Material |
N/A Aluminum |
Ingress Protection (IP) Rating |
N/A Ingress Protection (IP) 66/67 |
Jacket Material |
N/A Polyvinyl Chloride (PVC) |
Jacket Benefits |
N/A Liquid Tight |
Installation
N/A
|