Chlorinated polyethylene jacket with bonding wire through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type NWC. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" through 1-1/4". Jacket shall be black in color and be radiation-resistant. The outside of the jacket shall have a smooth appearance, Jacket material shall meet guidelines defined in IEEE 323-1974 and IEEE 383-1974.
Unit of Measure

Specifications

Type

N/A NWC

Electrical Trade Size

N/A 1/2 in16 mm

Length

N/A 100 ft30.48 m

Packaging

N/A Standard Carton

Inside Diameter

N/A 0.622 to 0.642 in15.799 to 16.307 mm

Outside Diameter

N/A 0.820 to 0.840 in20.828 to 21.336 mm

Approx. Inside Bend Radius

N/A 9.0 in228.6 mm

Approx. Weight per 100 ft

N/A 29 lbs13.15 kg

Color

N/A BLACK

N/A

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Polyethylene

Jacket Benefits

N/A Liquid Tight

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Suitable for use within nuclear containment areas.
  • Flexible metal core meets "Construction" requirements of UL Std. 360 sizes 3/8" through 4".
  • Radiation resistant jacket meets IEEE 323-1974 and IEEE 383-1974 guidelines.
  • Rated for temperature range of -40ºF to + 192ºF (-40ºC to +89ºC).
  • Manufactured in a full range of sizes from 3/8" through 4".

Application

N/A Nuclear Application or Where Radiation Protection is Necessary
Temperature Range: -40ºF to +192ºF (-40ºC to +89ºC)

Listing

N/A NUCLEAR PROCURMENT ISSUES COMMITTEE (NUPIC) NUPIC number 2651