Conduit shall be Anaconda SEALTITE® Type HTUA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.
Unit of Measure

Specifications

Type

N/A HTUA

Electrical Trade Size

N/A 1-1/2 in41 mm

Length

N/A 50 ft15.24 m

Packaging

N/A Small Cartons

Inside Diameter

N/A 1.575 to 1.600 in40.005 to 40.640 mm

Outside Diameter

N/A 1.865 to 1.900 in47.371 to 48.260 mm

Approx. Inside Bend Radius

N/A 5.5 in139.7 mm

Approx. Weight per 100 ft

N/A 112 lbs50.80 kg

Color

N/A GRAY

Optional Colors

N/A Black

Industry Certifications

N/A
UL Listed & CSA Certified

N/A

Cross-Reference #

N/A 55-28-87-02 6906-24-00 80252 ATLA-15

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Polyvinyl Chloride (PVC)

Jacket Benefits

N/A Extreme Cold High Heat Liquid Tight Oil Resistant

Installation

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations Rated for temperature ranges UL temps -51ºF to + 221ºF (-46ºC to +105ºC), CSA -51ºF to 167ºF (-46ºC to +75ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

NEC Articles

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Application

N/A Ideal for Use in Environments with Extreme Temperatures and UL Listing is Required
Temperature Range: -51ºF to +221ºF (-46ºC to +105ºC)